4102A Soft Case Model
4102A-H Hard Case Model
• The latest circuit design permits the instrument to operatewith the minimum of influence from earth voltage
and earth resistance of auxiliary earth spikes.
• Dust and drip proof. (designed to IEC 529 IP54)
• Earth resistance value can be read directly from the scale.
• Designed to meet IEC 61010-1 safety standard.
• Capable of measuring earth voltage.
• Small and lightweight. Shock resistant new case material.
• 2mA measuring current permits earth resistance tests
without tripping earth leakage current breakers
in the circuit under test.
• Lead wire connection to C and P terminals and proper
auxiliary earth resistance can be checked by "OK" lamp.
Lead wire connection to C and E terminals is good
when "OK" lamp is illuminated.
| 4102A Soft Case Model | 4102A-H Hard Case Model | 
|---|---|
![]()  | 
            ![]()  | 
        
| Measurement ranges | Earth Resistance: 0 - 12 Ω/0 - 120 Ω/0 - 1200 Ω Earth Voltage [50,60Hz]: 0 - 30V AC  | 
        
|---|---|
| Accuracy | Earth Resistance: ±3% of full scale Earth Voltage: ±3% of full scale  | 
        
| Overload protection | Earth Resistance: 276V AC for 10 seconds across 2 of the 3 terminals Earth Voltage: 276V AC for 1 minute  | 
        
| Applicable standards | IEC 61010-1 CAT III 300V Pollution Degree 2, IEC 61557 IEC 60529 IP54  | 
        
| Power source | R6 (AA) (1.5V) × 6 | 
| Dimensions | 105(L) × 158(W) × 70(D)mm | 
| Weight | 600g approx. | 
| Included Accessories | 7095A (Earth resistance test leads) × 1set (red-20m, yellow-10m, green-5m) 8032 (Auxiliary earth spikes) × 1set 7127A (Simplified measurement probe) × 1set R6 (AA) × 6 9121 (Shoulder strap) Instruction Manual Carrying case : 9084(Carrying case[Soft]:4102A only) : 9164(Carrying case[Hard]:4102A-H only)  | 
        
| Optional Accessories | 7100A (Precision measurement cord set) | 
                        