Fluke 1663 Multifunction Installation Tester

Harga :
CALL
Merk :
FLUKE
Pengiriman :
3 hari sejak pembayaran
Lokasi :
Jawa Barat - Bekasi
Dilihat :
64 Kali
Update Terakhir :
13-09-2016 10:33

Detail Produk

 The 1663 puts more power in your hands by quickly and efficiently testing to all local regulations, protecting appliances that may be inadvertently connected to the system under test, and making it easy to share test results over your smartphone.

Measurement functions

  • Continuity at L-N, N-PE inputs
  • Test smooth dc sensitive RCDs (Type B)
  • Earth resistance
  • Voltage & frequency
  • Wiring polarity checker, detects broken N wires
  • Insulation resistance
  • Continuity & resistance
  • Measure motor windings with continuity test
  • Loop & line resistance
  • Prospective earth fault current (PEFC/IK)
  • Prospective short-circuit current (PSC/IK)
  • RCD switching time
  • RCD tripping level (ramp test)
  • Measures trip time & current for RCD type A & AC in one test
  • RCD variable current
  • Automatic RCD test sequence
  • Phase sequence indicator

Other features

  • On/Off switchable auto-start for RCD & looptest
  • Self-test
  • Illuminated display

Memory interface

  • Z Max Memory
  • Memory
  • Computer Interface (when used with optional FlukeView & Fluke DMS software)
  • Time and date (when used with optional FlukeView software)

Included accessories

  • Heavy duty, single input line cord
  • Hard case
  • Remote control probe
  • Zero adapter
  • Withstands a drop of 1 meter
  • Compact, lightweight (less than 1.3 kg) and padded neck-strap to free your hands for all day testing

SPECIFICATION 

AC voltage measurement
Range 500 V
Resolution 0.1 V
Accuracy 45 Hz – 66 Hz 0.8% + 3
Input impedance 360 kΩ
Overload protection 660 V rms
Continuity testing (RLO)
Range (autoranging) 20 Ω / 200 Ω / 2000 Ω
Resolution 0.01 Ω / 0.1 Ω / 1 Ω
Open Circuit Voltage >4 V
Insulation resistance measurement (RISO)
Test voltages 50-100-250-500-1000 V
Accuracy of tTest voltage (at rated test current) +10%, -0%
Test voltage 50 V
100 V
250 V
500 V
1000 V
Insulation resistance range 20 MΩ /50 MΩ
20 MΩ / 100 MΩ
20 MΩ / 200 MΩ
20 MΩ / 200 MΩ / 500 MΩ
20 MΩ / 200 MΩ / 1000 MΩ
Resolution 0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ / 1 MΩ
0.01 MΩ / 0.1 MΩ / 1 MΩ
Test current 1 mA @ 50 kΩ
1 mA @ 100 kΩ
1 mA @ 250 kΩ
1 mA @ 500 kΩ
1 mA @ 1 MΩ
Loop and line impedance (ZI)
Range 10 Ω / 0.001 Ω / High current mΩ mode
Resolution 0.01 Ω / 0.1 Ω / 1 Ω
Prospective earth fault current, PSC test
Range 1000 A / 10 kA (50 kA)
Resolution 1 A / 0.1 kA
Computation Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively.
RCD testing, RCD types tested
RCD Type AC¹
G²,S³
Model 1663 A4, AC¹, G²,S³
Notes ¹Responds to AC 
²General, no delay
³Time delay
4Responds to pulsed signal
5Responds to smooth DC signal
Tripping speed test (ΔT)
Current settings¹ 10-30-100-300-500-1000 mA – VAR
10-30-100 mA
Multiplier x ½, x 1
x 5
Measurement range RCD Type G 310 ms
50 ms
RCD Type S 510 ms
160 ms
Notes ¹1000 mA type AC only
700 mA maximum type A in VAR mode
VAR mode not available for type B.
RCD/FI-Tripping Current Measurement/Ramp Test (IΔN)
Current range 30% to 110% of RCD rated current¹
Step size 10% of IΔN²
Dwell time Type G 300 ms/step
Type S 500 ms/step
Measurement accuracy ±5%
Specified trip current ranges (EN 61008-1) 50% to 100% for Type AC
35% to 140% for Type A (>10 mA)
35% to 200% for Type A (≤10 mA)
50% to 200% for Type B
²5% for Type B
Notes ¹30% to 150% for Type A IΔN > 10 mA
30% to 210% for Type A IΔN = 10 mA
20% to 210% for Type B
Earth Resistance Test (RE)
Range 200 Ω / 2000 Ω
Resolution 0.1 Ω / 1Ω
Frequency 128 Hz
Output Voltage 25 V
Phase Sequence Indication
Icon icon phase sequence indicator  Phase Sequence indicator is active.
General Specifications
Size (L x W x H) 10 x 25 x 12.5 cm
Weight (incl. batteries) 1.3 Kg
Battery size, quantity Type AA, 6 ea.
Sealing IP-40
Safety Complies with EN61010-1 Ed 2.0 (2001-02), UL61010, ANSI/ISA –s82.02.01 2000 and CAN/CSA c22.2 No. 1010 2nd edition
Overvoltage CAT III / 500V; CAT IV 300V
Performance EN61557-1 to EN61557-7 Second Edition and EN61557-10 Second Edition