 Specification

Product Specifications
Volt Model Measurement Range Resolution Accuracy
Vrms (AC + DC) 1 V to 1000 V phase to neutral 0.1 V ±0.5% of nominal voltage4
Vpk 1 Vpk to 1400 Vpk 1 V 5% of nominal voltage
Voltage Crest Factor (CF) 1.0 > 2.8 0.01 ±5%
Vrms½ 1 V to 1000 V phase to neutral 0.1 V ±1% of nominal voltage
Vfund 1 V to 1000 V phase to neutral 0.1 V  ±0.5% of nominal voltage
Amps (accuracy excluding clamp accuracy)
Amps (AC + DC) i430-Flex 1x 5 A to 6000 A 1 A ±0.5% ±5 counts
i430-Flex 10x 0.5 A to 600 A 0.1 A ±0.5% ±5 counts
1 mV/A 1x 5 A to 2000 A 1 A ±0.5% ±5 counts
1 mV/A 10x 0.5 A A to 200 A (AC only) 0.1 A ±0.5% ±5 counts
Apk i430-Flex 8400 Apk 1 Arms ±5%
1 mV/A 5500 Apk 1 Arms ±5%
A Crest Factor (CF) 1 to 10 0.01 ±5%
Amps½ i430-Flex 1x 5 A to 6000 A 1 A ±1% ±10 counts
i430-Flex 10x 0.5 A to 600 A 0.1 A ±1% ±10 counts
1 mV/A 1x 5 A to 2000 A 1 A ±1% ±10 counts
1 mV/A 10x 0.5 A A to 200 A (AC only) 0.1 A ±1% ±10 counts
Afund i430-Flex 1x 5 A to 6000 A 1 A ±0.5% ±5 counts
i430-Flex 10x 0.5 A to 600 A 0.1 A ±0.5% ±5 counts
1 mV/A 1x 5 A to 2000 A 1 A ±0.5% ±5 counts
1 mV/A 10x 0.5 A A to 200 A (AC only) 0.1 A ±0.5% ±5 counts
Hz
Fluke 434 @ 50 Hz nominal 42.50 Hz to 57.50 Hz 0.01 Hz ±0.01 Hz
Fluke 434 @ 60 Hz nominal 51.00 Hz to 69.00 Hz 0.01 Hz ±0.01 Hz
Power
Watts (VA, var) i430-Flex max 6000 MW 0.1 W to 1 MW ±1% ±10 counts
1 mV/A max 2000 MW 0.1 W to 1 MW ±1% ±10 counts
Power Factor (Cos j/DPF) 0 to 1 0.001 ±0.1% @ nominal load conditions
Energy
kWh (kVAh, kvarh) i430-Flex 10x Depends on clamp scaling and V nominal ±1% ±10 counts
Energy Loss i430-Flex 10x Depends on clamp scaling and V nominal ±1% ±10 counts Excluding line resistance accuracy
Harmonics
Harmonic Order (n) DC, 1 to 50 Grouping: Harmonic groups according to IEC 61000-4-7
Inter-Harmonic Order (n) OFF, 1 to 50 Grouping: Harmonic and Interharmonic subgroups according to IEC 61000-4-7
Volts % f 0.0% to 100% 0.1% ±0.1% ±n x 0.1%
r 0.0% to 100% 0.1% ±0.1% ±n x 0.4%
Absolute 0.0 to 1000 V 0.1 V ±5%1
THD 0.0% to 100% 0.1% ±2.5%
Amps % f 0.0% to 100% 0.1% ±0.1% ±n x 0.1%
r 0.0% to 100% 0.1% ±0.1% ±n x 0.4%
Absolute 0.0 to 600 A 0.1 A ±5% ±5 counts
THD 0.0% to 100% 0.1% ±2.5%
Watts % f or r 0.0% to 100% 0.1% ±n x 2%
Absolute Depends on clamp scaling and V nominal ±5% ±n x 2% ±10 counts
THD 0.0% to 100% 0.1% ±5%
Phase Angle -360° to +0° ±n x 1°
Flicker
Plt, Pst, Pst (1 min) Pinst 0.00 to 20.00 0.01 ±5%
Unbalance
Volts % 0.0% to 20.0% 0.1% ±0.1%
Amps % 0.0% to 20.0% 0.1% ±1%
Mains Signaling
Threshold Levels Threshold, limits and signaling duration is programable for two signaling frequencies
Signaling Frequency 60 Hz to 3000 Hz 0.1 Hz  
Relative V % 0% to 100% 0.10% ±0.4%
Absolute V3s (3 second avg.) 0.0 V to 1000 V 0.1 V ±5% of nominal voltage
General Specifications
Case Design Rugged, shock proof with integrated protective holster Drip and dust proof IP51 according to IEC60529 when used in tilt stand position Shock and vibration Shock 30 g, vibration: 3 g sinusoid, random 0.03 g 2 /Hz according to MIL-PRF-28800F Class 2
Display Brightness: 200 cd/m 2 typ. using power adapter, 90 cd/m 2 typical using battery power Size: 127 x 88 mm (153 mm/6.0 in diagonal) LCD Resolution: 320 x 240 pixels Contrast and brightness: user-adjustable, temperature compensated
Memory 8 GB SD card (SDHC compliant, FAT32 formatted) standard, upto 32GB optionally Screen save and multiple data memories for storing data including recordings (dependent on memory size)
Real-Time Clock Time and date stamp for Trend mode, Transient display, System Monitor and event capture
Environmental
Operating Temperature 0°C ~ +40°C; +40°C ~ +50°C excl. battery
Storage Temperature -20°C ~ +60°C
Humidity +10°C ~ +30°C: 95% RH non-condensing 
+30°C ~ +40°C: 75% RH non-condensing 
+40°C ~ +50°C: 45% RH non-condensing
Maximum Operating Altitude Up to 2,000 m (6666 ft) for CAT IV 600 V, CAT III 1000 V 
Up to 3,000 m (10,000 ft) for CAT III 600 V, CAT II 1000 V 
Maximum storage altitude 12 km (40,000 ft)
Electro-Magnetic-Compatibility (EMC) EN 61326 (2005-12) for emission and immunity
Interfaces Mini-USB-B, Isolated USB port for PC connectivity SD card slot accessible behind instrument battery
Warranty Three years (parts and labor) on main instrument, one year on accessories


 


Features 
  • Troubleshoot Real-Time: Analyze the trends using the cursors and zoom tools.
  • Automatic Trending: Every measurement is always automatically recorded, without any set-up.
  • Logger Function: Configure for any test condition with memory for up to 600 parameters at user defined intervals.
  • Measure All Three Phases and Neutral: With included four flexible current probes with enhanced thin flex design to fit into the tightest places.
  • Power Inverter Efficiency: Simultaneously measure AC output power and DC input power for power electronics systems using optional DC clamp.
  • Energy Loss Calculator: Classic active and reactive power measurements, unbalance and harmonic power, are quantified to pinpoint the fiscal costs of energy losses.
  • Highest Safety Rating in the Industry: 600 V CAT IV/1000 V CAT III rated for use at the service entrance.
  • System-Monitor: Ten power quality parameters on one screen according to EN50160 power quality standard.
  • View Graphs and Generate Reports: With included analysis software.
  • Battery Life: Seven hours operating time per charge on Li-ion battery pack.